2305 Pleasant View Rd. Middleton Industrial Park Middleton, WI 53562
PH: (608) 831-2585
FAX (608) 831-7407
I0000145.DOC Rev 3
21.6 - 26.4 VAC Input / 4 - 20mA Output
18 - 36 VDC or 21.6 - 26.4 VAC Input / 0 - 10 VDC Output15 - 36 VDC or 21.6 - 26.4 VAC Input / 0 - 5 VDC Output
Figure # 9
15 - 36 VDC Supply Voltage or
21.6 - 26.4 VAC Supply Voltage
Supply Ground / Common
VDC
0 - 5 VDC Output
J2
Vout
GND
4-20
Red Wire
4 65
32
1
ON
SW3
Green Wire
BLK Wire
4
ON
32
1
SW2
Zero
Span
18 - 36 VDC Supply Voltage or
21.6 - 26.4 VAC Supply Voltage
0 - 10 VDC Output
Supply Ground / Common
15 - 36 VDC Input / 4 - 20mA Output
4 - 20mA Output
15 - 36 VDC Supply Voltage
J2
Vout
VDC
GND
4-20
Green Wire
5
Red Wire
BLK Wire
6
SW2
4
32
1
ON
ON
4
SW3
32
1
Supply Ground / Common
21.6 - 26.4 VAC Supply Voltage
4 - 20mA Output
Zero
Span
Red Wire
654
2 3
1
ON
VDC
SW3
J2
Green Wire
BLK Wire
Vout
GND
4
SW2
ON
2 3
1
4-20
Zero
Span
Red Wire
BLK Wire
654
2 3
1
ON
SW2
J2
Vout
Green Wire
VDC
GND
4-20
4
ON
SW3
2 3
1
Zero
Span
Temperature Sensor Connections (For RH/Temperature Sensor Combination Units only)
All of the connections to the temperature sensor connections should be made to the (2 or 3) 22 AWG 24” Flying Lead
wires using wire nuts or crimp style connectors. Please note that the wire colors will change depending on the type and
value of the sensing element used.
Duct Mounting Configuration:
The RH transmitter should be placed away from areas of excessive moisture, corrosive fumes, vibration, or extremely high
temperatures. All of the RH sensors have a +/- 3% interchangeability. It is recommended to do a single point calibration
for a much higher accuracy.
1. Drill a ¾” diameter hole in the duct where the sensor is to be mounted.
2. Now insert the stainless steel probe into the hole until the foam is in direct contact with the duct and attach
the RH transmitter by using the (2) #8 x ¾” self tapping TEK screws that are included with the installation
instruction.
3. Remove the cover and install your conduit connectors or watertight fittings. The outer ring should be used
when using a ½” NPT conduit fitting. Please note that the inner ring will knockout first and then the outer
ring should be tapped in (1) or (2) locations with a screwdriver before it can be peeled out. The cover will
be connected to the housing by the RH sensor leads. To remove the RH sensor leads from the housing
see Figure #8.
4. Next connect all of the wires to the corresponding terminal blocks and/or flying leads the wires to the
corresponding terminal blocks as shown in Figure #7 and Figure #9.
5. Now make sure that all of the dipswitches are properly configured as per Figures #2, #3, #5, and #6 before
initially powering the unit.