Installation and Operation Instructions
ACI/592, ACI/592-10K
ACI/592-CS, ACI/592-10K-CS
2305 Pleasant View Rd. Middleton Industrial Park Middleton, WI 53562
PH: (608) 831-2585 FAX: (608) 831-7407
II-19
A
C
I
utomation
omponents
nc.
READ THESE INSTRUCTIONS BEFORE YOU BEGIN INSTALLATION
All ACI/592 and ACI/592-10K semiconductor sensors are both polarity and non-position sensitive. All semiconductor
sensor type room units are supplied with a two or three pole terminal block depending on whether they have a current or
voltage output.
The following units are available with corresponding terminal blocks for all connections: Room with Setpoint (RS),
Room with Override (RO), Room with Setpoint and Override (RSO), and Room with Setpoint, Override, and RJ12
Communication Jack (RSO RJ12).
All other configurations are supplied with 22 gauge lead wires and can be hooked up with any crimp style or wire nut wire
connectors.
n TROUBLESHOOTING
Sensor reads 0 uA or VDC Check supply Voltage - Sensor or wires are shorted together open
Sensor reads supply voltage or high current Sensor or wires are shorted together
Erratic readings Bad wire connections - Condensation or Moisture problem – RF Noise
nWIRING DIAGRAMS
J2
Short Senso r
Separate Input
SW1
+ - SEN O/R SET
1 2 3 4 5 6
6
1
6 Pin RJ12
Communication Jack
Power Supply Common or
Ground
+15 VDC Supply Voltage
for Sensor
uA or VDC Sensor Output to
Controller or System
Tenant Override or Dry Contact Output
to Controller
(Separate Input Only)
Setpoint Resistance Output to Controller
(CS Version has a 2.732 t o 3.332 VDC Output)
Terminals for RJ12 Communications
J3
Membrane
Wire Access Hole
“After Hours” Normally-Open
Override Switch
Override Shorts Separate Input
Sensor
(Dry Contact Closure
)
Figure #1
Override Options Jumper Settings (J3)
Short Senso
r
Separate Input
Short Senso
r
Separate Input
**Note: All Room with Override (RO) and Room with Setpoint and Override (RSO) sensors are shipped with the
Override in parallel with the sensor unless specified otherwise. If a separate Input or Tenant Override is
Needed, see Figure #1 for the Override Options jumper Settings.
** NOTE: (J2) is only used for Connection of the Membrane Switch.
CSI Rev 7