Installation and Operation Instructions
ACI/TT100, ACI/TT1000
ACI/TTM100, ACI/TTM1000
ACI/TTU100, ACI/TTU1000
2305 Pleasant View Rd. Middleton Industrial Park Middleton, WI 53562
PH: (608) 831-2585 FAX: (608) 831-7407
II-21
A
C
I
utomation
omponents
nc.
READ THESE INSTRUCTIONS BEFORE YOU BEGIN INSTALLATION
WIRING
Power RTD
24VDC
OR
24 VAC*
1-5VDC
2-10VDC
Out
p
ut
Power RTD
4-20mA
Out
+24 VDC
4 to 20 mA Current Output
+
24VDC
-
Current
4-20mA
Voltage
1-5
,
2-10VDC
Room Transmitter
with Setpoint and Override
Analog Input Common
For the 4-20 mA
Setpoint Only!
O/R
+
Set
-
-
T
+
4 to 20 mA Temperature
Output to Controller
+8 to 35 VDC
All ACI/TT and TTM temperature transmitters can be powered from either an unregulated or regulated +8 to 35VDC
power supply. Several transmitters may be powered from the same supply as shown below. Each transmitter could
draw 22mA. To determine the number of transmitters use the following formula:
N =
I
mA22
where: N = number of transmitters
I = current available from power supply
22mA = maximum current draw of transmitter
e.g., If I = 1.5A then:
N = 1.5/22mA
N = 68
Therefore a 1.5A power supply will safely power up to 68 transmitters.
All ACI/TT, TTM, and ACI/TTU temperature transmitters are non-polarity sensitive. That means that either the
positive and negative outputs of the power supply can be connected to either side of the power terminal block. ACI
transmitters will also accept AC power only if specified when ordering. The output must be specified as a +1-5 or
+2-10 for this option when ordering the transmitters.
Power Supply
+ - + - + -
Temp.Transmitter #1 Temp.Transmitter #N Temp.Transmitter #2
-
VDC
+
Controller
Gnd In1 In2 In3
= Connections
In1 = Controller Input #1
In2 = Controller Input #2
In3 = Controller Input #3
* Must be ordered as 24 VAC input
Vue de la page 0
1 2 3 4 5 6 7 8

Résumé du contenu

Page 1 - In3 = Controller Input #3

Installation and Operation Instructions ACI/TT100, ACI/TT1000 ACI/TTM100, ACI/TTM1000

Page 2 - I0000145 Rev1.Doc

2305 Pleasant View Rd.  Middleton Industrial Park  Middleton, WI 53562 PH: (608) 831

Page 3

1234ON45632ON1SW2SW3J24-20VACGND0-5VmAor orVDC0-10VRed WireBLK WireGreen Wire4SW3ON321mA4-200-10V0-5VSW22VDCorVAC65GND43Red WireON1orGreen WireJ2BLK

Page 4

2305 Pleasant View Rd.  Middleton Industrial Park  Middleton, WI 53562 PH: (608) 831-2585  FAX (608) 831-7407 I0000145 Rev1.Doc Decrement RH O

Page 5

+15 to 36 VDC Input / 4 to 20mA Output+15 to 36 VDC Input / 0 to 5 VDC Output+24 VAC Input / 0 to 10 VDC Output+24 VAC Input / 4 to 20mA Output+15 to

Page 6 -  RH Conversion Formulas

2305 Pleasant View Rd.  Middleton Industrial Park  Middleton, WI 53562 PH: (608) 831-2585  FAX (608) 831-7407 I0000145 Rev1.Doc 5. Now make su

Page 7

2305 Pleasant View Rd. Middleton Industrial Park Middleton, WI 53562 PH: (608) 831-2585 FAX: (608) 831-7407 II-22 nROOM TEMPERATURE TRANS

Page 8 - To Controller

2305 Pleasant View Rd. Middleton Industrial Park Middleton, WI 53562 PH: (608) 831-2585 FAX: (608) 831-7407 II-23 nTROUBLESHOOTING No readi