Installation and Operation Instructions
ACI/RH TUCH LCD Room Unit
GENERAL INFORMATION
The ACI/RH TUCH LCD Room Unit is factory-
configured to support your specific requirements.
CAUTION
CHECK THAT THE ACI/RH TUCH LCD ROOM
UNIT IS CORRECTLY CONFIGURED FOR THE
APPLICATION; CONTACT ACI IF YOU ARE
UNSURE.
THE ACI/RH TUCH LCD ROOM UNIT IS A
PRECISION INSTRUMENT; PLEASE HANDLE
IT WITH CARE!
MOUNTING INSTRUCTIONS
Separate the cover from the base. Attach the base
directly to drywall, or to a standard 2” x 4” junction box
using the mounting hardware provided. Refer to the
wiring instructions to make the necessary connections.
After wiring, attach the cover to the base and turn the
(2) hex-screws at the bottom of the base until the cover
cannot be removed.
WARNING
REMOVE POWER BEFORE WIRING! NEVER
CONNECT OR DISCONNECT WIRING WITH
POWER APPLIED. DO NOT ALLOW LIVE
WIRES TO TOUCH THE CIRCUIT BOARD!
CAUTION
WIRING MUST COMPLY WITH APPLICABLE
LOCAL AND NATIONAL ELECTRICAL
REGULATIONS.
DO NOT RUN THE ACI/RH TUCH LCD ROOM
UNIT WIRING IN ANY CONDUIT WITH
MAINS POWER SYSTEM WIRING.
ACI RECOMMENDS USING A SEPARATE UL-
LISTED CLASS 2 TRANSFORMER WHEN
POWERING THE ACI/RH TUCH LCD ROOM
UNIT WITH 24VAC! FAILURE TO WIRE
DEVICES WITH THE CORRECT POLARITY
WHEN USING A SHARED TRANSFORMER
MAY RESULT IN DAMAGE TO ANY DEVICE
POWERED BY THE SHARED TRANSFORMER.
WIRING INSTRUCTIONS
The number of wires needed to connect the ACI/RH
TUCH LCD Room Unit to a controller depends on the
application. Most applications require three wires to
support the RH output, power, and ground (common).
All signals are common ground referenced. ACI
recommends 16-22 AWG twisted pair wires or
shielded cable for all sensor installations. Be sure to
connect the cable shield to the ground at the
controller ONLY.
WIRING DIAGRAM
RH/FAN
RH signal to controller.
COM (-)
Ground or signal common, 20-28Vac (-).
POWER (+)
+15 to +30VDC, or 20-28Vac (+). See notes.
NOTES:
1. If the ACI/RH TUCH LCD Room Unit has any output configured as 0-10V
or 2-10V, the voltage at the POWER(+) terminal must be at least +18VDC.
Vue de la page 0
1 2 3

Résumé du contenu

Page 1 - ACI/RH TUCH LCD Room Unit

2305 Pleasant View Rd. ● Middleton Industrial Park ● Middleton, WI 53562 PHONE (608) 831-2585 ● FAX (608) 831-7407 I0000511 REV 1 11/13/2008 Pag

Page 2

2305 Pleasant View Rd. ● Middleton Industrial Park ● Middleton, WI 53562 PHONE (608) 831-2585 ● FAX (608) 831-7407 I0000511 REV 1 11/13/2008 Pag

Page 3

2305 Pleasant View Rd. ● Middleton Industrial Park ● Middleton, WI 53562 PHONE (608) 831-2585 ● FAX (608) 831-7407 I0000511 REV 1 11/13/2008 Pag

Commentaires sur ces manuels

Pas de commentaire